Skip to content
V2L Workshop

G98 vs G99 — when does V2L trigger DNO notification?

ENA G98/G99 govern equipment that runs in parallel with the public grid. A true islanded V2L feed — physically separated by a changeover so it can never run in parallel or export — is generally outside G98/G99 and is treated as a load. The moment a system can export or synchronise (true V2G/V2H), it is in scope: G98 is the lighter notify-not-approve route for small type-tested microgenerators within the G98 scope threshold, G99 covers larger or island-capable systems and generally needs DNO acceptance before energising. The exact G98/G99 clause locators are Not confirmed pending the official PDFs.

In short

  • G98/G99 apply to equipment running in parallel with the grid; true islanded V2L (changeover, no export) is generally outside them, treated as a load.
  • G98 = notify-not-approve for small, type-tested microgenerators within the G98 scope threshold, in parallel.
  • G99 = larger or island-capable; generally needs DNO acceptance before energising.
  • G99 Issue 2 brings electricity storage incl. V2G EVs into scope — new mandatory storage requirements from 1 March 2026.
  • Exact G98/G99 clause/section locators are Not confirmed (pending the official PDFs); whether a changeover truly prevents parallel operation is a design-and-test matter.

Where this stops: This explains when the DNO regime applies. Whether a given changeover genuinely prevents parallel operation, and the connection application itself, are competent-person and DNO matters.

Not yet confirmed on this page

Some details below depend on sources still being verified against the published standard, so we mark them Not confirmed rather than guess:

The trigger is parallel operation

G98 and G99 govern equipment that operates in parallel with — synchronised to — the public network. A pure islanded V2L feed, physically separated by a changeover so there is no possibility of back-feed, is generally not a parallel connection. The card's clearest hook: where an EV/charger cannot operate as a V2G EV (cannot export or parallel), it is treated as a load, outside G99.

Running a source in parallel with the grid engages ENA G98/G99 (DNO notification); a true islanded changeover that never connects the two together is generally treated as a load, outside G98/G99.

What the diagram shows: Two arrangements. On the left, the grid and the EV/source are connected together (in parallel) — this engages ENA Engineering Recommendations G98/G99, so the DNO must be notified. On the right, a break-before-make changeover switch connects the load to either the grid OR the EV/source, never both together (islanded) — a source that can never run in parallel or export is generally treated as a load and sits outside G98/G99. Whether a given changeover genuinely prevents parallel operation is a design-and-test matter for the competent person and the DNO. The exact G98/G99 clause locators are Not confirmed pending the official PDFs. Legend (stated in words, not colour alone): L = line/live conductor; N = neutral; E/CPC = earth / circuit protective conductor.

G98 vs G99

G99 Issue 2 expressly brings electricity storage, including V2G EVs, into scope, with new mandatory storage requirements recorded as in force from 1 March 2026 — relevant when timing any grid-parallel V2H/V2G advice.

Not confirmed

The exact G98/G99 Issue 2 clause/section numbers are not yet confirmed against the official ENA PDFs; the citation/edition is checked (public-primary) while the clause substance is pending a licensed/source-text check, so we render precise locators Not confirmed. Whether a given changeover genuinely prevents parallel operation (a momentary parallel transfer can pull it back into scope) is a design-and-test matter for the competent person and the DNO.

How this is made and proven compliant

What governs it
  • ENA EREC G98 / G99 (parallel connection of generation/storage) + G100 (export/import limitation)
  • BS 7671 §551.7 (parallel operation) for the installation side
Who may do it

A competent person determines whether the arrangement is grid-parallel or genuinely islanded, and makes any G99 connection application; the DNO accepts the connection where required.

How compliance is demonstrated
  • Establish whether the system can export/parallel (in scope) or only island via a break-before-make changeover (out of scope)
  • For grid-parallel: a G98 notification or a G99 connection application accepted by the DNO before energising
  • Prove the changeover genuinely prevents parallel operation (design and test)
Confidence & currency

Confidence: Inference rolled up across the clauses cited above (the strictest state wins).

Frequently asked questions

Do I need to tell the DNO about a V2L backup?

Generally not, if it is a true island that can never export or run in parallel (separated by a break-before-make changeover) — it is treated as a load. The moment it can export or synchronise (V2G/V2H), G98 or G99 applies and you must notify or apply to the DNO.

What's the difference between G98 and G99?

G98 is a lighter notify-not-approve route for small type-tested microgenerators within the G98 scope threshold. G99 covers larger or island-capable systems and generally needs DNO acceptance before energising.

Why don't you quote the exact G99 section numbers?

The official G98/G99 Issue 2 PDFs are not yet in our reference library, so we treat exact section numbers as inference and render them Not confirmed rather than cite numbers we have not verified.

Last reviewed
14 June 2026
Written against
BS 7671:2018 + A4:2026
Reviewed by
Martin (qualified UK electrician)
Next review due
14 December 2026

General information, not project-specific design advice. Standards are cited by reference only and never reproduced. How we source this.

References & sources (2)
  1. ENA — connecting generation/storage to the networksexact G98/G99 locators Not confirmed pending the official PDFs
  2. ENA G98/G99 forms