Skip to content
V2L Workshop

Earthing & bonding fundamentals for V2L

Every electrical source needs exactly one neutral-earth reference. The grid's is made for you at the substation; a floating V2L output has none, so a single bond must be supplied at the source side, in circuit only when on V2L — never two bonds in parallel. The protective conductor (earth) stays continuous and is never switched. Main and supplementary bonding tie the installation's metalwork to one potential. Which earthing arrangement you use depends on where the board is: a separate outbuilding is made TT with a local electrode; an indoor board keeps the single PME/MET earth and uses an isolation transformer. It must be designed and proven by test by a competent person, and the vehicle manufacturer does not sanction this use.

In short

  • One source, one neutral-earth reference. The grid's lives at the substation; a floating V2L output has none until you supply one.
  • Make exactly one bond, on the source side, in circuit only on V2L — never two earth references in parallel.
  • The protective conductor (CPC/earth) is continuous and never switched — you switch line and neutral, not earth.
  • Main and supplementary bonding keep the installation's metalwork at one potential (BS 7671 Chapter 54 — §542 earthing arrangements, §544 bonding conductors).
  • Prove it by test: RCD operation in both grid and V2L modes; for a TT island, a low and stable electrode resistance (Ra).
  • Outbuilding → TT with a local electrode; indoors → isolation transformer keeping the one PME/MET earth. Designed and proven by a competent person.

Where this stops: This explains the earthing principle that governs every V2L decision. It is not a wiring recipe — the earthing arrangement, the bonding and the testing are for a competent person to design and prove.

Not yet confirmed on this page

Some details below depend on sources still being verified against the published standard, so we mark them Not confirmed rather than guess:

Education, not an instruction to carry out the work

This explains the principle. Electrical installation work of this kind is notifiable and must be designed, installed and tested by a competent person to the current edition of BS 7671. The floating-V2L-on-PME approach is contested — it is only ever valid designed and proven by test, and the vehicle manufacturer does not sanction it.

The one principle behind every V2L earthing decision

Every electrical source needs exactly one neutral-earth reference. On the public supply that reference is made for you: the star point of the substation transformer is earthed, and the network brings that reference to your home (on most modern UK supplies as a PME / TN-C-S arrangement). A car's V2L output is a *separately derived* source. On the Hyundai Ioniq 5 it is reported to be floating — there is no internal bond between its neutral and earth — so until you supply one, there is nothing for an earth fault to flow back to and nothing for an RCD to operate against.

Confidence: Inference The Ioniq 5 V2L output is floating (no internal neutral-earth bond).

Reported in field accounts and consistent with the design, but behaviour varies by adapter. The safe default is to treat the output as floating until it is bench-verified, because an RCD has nothing to operate against until a single bond exists.

A floating V2L output has no neutral-earth reference, so an RCD cannot operate; making a single neutral-earth bond on the source side establishes the reference and restores protection.

What the diagram shows: Two states side by side. On the left, the V2L source as delivered is floating: line (L) and neutral (N) have no neutral-earth (N–E) reference, so a residual current device has nothing to operate against — the output passes a socket tester but offers no shock protection. On the right, a single N–E bond is made on the source side (only when on V2L): this establishes the earth reference so the RCD can operate. Make exactly one bond, never two in parallel. Bonding the V2L neutral to earth feels wrong but is correct — it is the source's earth reference, like the substation transformer's earthed star point. Legend (stated in words, not colour alone): L = line/live conductor; N = neutral; E/CPC = earth / circuit protective conductor.

A floating output looks fine but is not protected

A floating V2L output passes a plug-in socket tester — yet it offers no RCD protection until the single neutral-earth bond exists. That is the dangerous 'looks fine' case the principle exists to close.

One bond — and only one

Supplying that reference means bonding the V2L neutral to earth. It feels wrong — you have spent a career keeping live conductors away from earth — but it is correct: it is the exact equivalent of the substation transformer's earthed star point, just for your separately derived source. The rule is one source, one bond. The bond is made on the source side, and it is in circuit only when you are on V2L (typically through an auxiliary contact on the V2L contactor), so that you never have two earth references fighting in parallel — one at the substation, one at the car — at the same time.

§551.4.3.2.1BS 7671Confidence: Inference

A source supplying in island mode or as a switched alternative needs an independent means of earthing — it must not rely solely on the distributor's earth, which can be disconnected during network maintenance.

Reference only — verify against the current edition; standard text is not reproduced.

The protective conductor is continuous — you never switch the earth

A changeover switches line and neutral between grid and V2L. It must never switch the protective conductor (the earth / CPC). Earth stays continuous from every exposed-conductive-part back to the main earthing terminal at all times, in both modes and during the transfer itself. What changes between modes is *where the single neutral-earth reference is made* — never whether an earth exists. Switching a protective conductor would leave metalwork unearthed for the instant it matters most.

Switch L and N — keep E continuous

Two-pole changeover of line and neutral; the protective conductor is bonded through, continuous, and never broken by a switch contact. The neutral-earth bond is the only earth-side element that changes, and it is made only on V2L.

Main and supplementary bonding

Bonding is what keeps everything that *can* be touched at the same potential, so there is no dangerous voltage difference to bridge. Main protective bonding ties incoming metallic services (water, gas, structural steel) to the main earthing terminal. Supplementary bonding ties exposed- and extraneous-conductive-parts together locally where required. On a PME supply this matters even more, because a broken PEN on the network can lift all 'earthed' metalwork together — bonding ensures it rises *together*, removing the touch-voltage difference rather than leaving one part live relative to another.

Chapter 54 (§542, §544)BS 7671Confidence: Inference

§542 sets the earthing arrangements (earthing conductor, main earthing terminal, electrodes); §544 sets the protective bonding conductors and their sizing. The V2L earthing decision is a Chapter 54 decision, made by the designer and proven by test.

Reference only — verify against the current edition; standard text is not reproduced.

Bonding-conductor sizing is set by Chapter 54 and its tables, against the size of the supply conductors — cited here by reference only, not reproduced. It is part of what the competent person calculates and records.

Where the board is decides the arrangement

The single-reference principle is the same everywhere; how you realise it depends on where the essential board sits. There are two clean routes, and the full decision tree (with the diagrams) lives on the island-mode and method pages.

Separate outbuilding → make it TT

Drive a local earth electrode and take every circuit protective conductor to the outbuilding's earth bar — continuous, never switched. Do not export the dwelling's PME earth to the outbuilding (broken-PEN risk); only line and neutral run over. Make the single V2L neutral-earth bond through a contactor auxiliary contact, so it exists only on V2L, and protect with a Type A RCD. This only holds if no metal pipe, structure or cable armour bridges the two earth systems — a stray metallic path silently re-imports the PME earth you were trying to keep out.

Earth-electrode design (with BS 7671 §542.2.2 / §542.2.4, Table 41.5)BS 7430Confidence: Inference

Electrode type, depth, soil resistivity and rod spacing set the earth resistance. Keep Ra as low and stable as practicable — an electrode with a high electrode resistance tends to drift across the seasons, which is the difference between an island that disconnects safely and one that does not.

Reference only — verify against the current edition; standard text is not reproduced.

Inside the dwelling → isolation transformer, keep the one earth

You cannot TT a single indoor sub-board: it creates a simultaneous-reach hazard with the rest of the PME-earthed installation — you could touch the TT-referenced metalwork and the PME-referenced metalwork at once. Indoors you keep one earth. An isolation transformer in the V2L feed galvanically separates the floating output; the single neutral-earth bond is made on the transformer secondary (on V2L), and the protective conductor stays continuous to the main earthing terminal. No second electrode, no neutral diversion, no indoor TT island.

On a PME (TN-C-S) supply the V2L island gets its own earth reference — the CPC stays continuous, the neutral-earth bond is switched in only on V2L, and a local electrode provides the earth.

What the diagram shows: The diagram shows two sources feeding an essential board through a changeover. From the grid, line (L) and neutral (N) arrive at the changeover; the circuit protective conductor (E/CPC) runs continuously to the board and earth bar and is never switched. From the V2L source, L and N arrive at the other side of the changeover. A neutral-earth (N–E) bond is made only when the board is on V2L, providing the floating output its single earth reference. A local earth electrode connects to the earth bar. The point: every source has exactly one neutral-earth reference, and the protective conductor is continuous in both switch states. Legend (stated in words, not colour alone): L = line/live conductor; N = neutral; E/CPC = earth / circuit protective conductor.

Proof is by test, not by reasoning

None of the above is settled by being correct on paper — it is settled by test. The earthing and bonding are proven, in both grid and V2L modes, before the arrangement is relied on.

Where this fits

This page is the principle. For the branching design — outbuilding TT versus indoor isolation transformer — see the island-mode earthing and isolation-transformer pages; for why a floating output is the starting condition, see the floating-versus-bonded page; and for the whole journey end to end, see the cornerstone.

Not confirmed · safety-critical

Whether Amendment 4:2026 changed anything for §722 / V2X / PME / open-PEN is Not confirmed — the public IET/BSI change material checked here does not identify a §722 / V2X / PME / open-PEN change in A4:2026. The existing §722 / PME / open-PEN material appears to carry forward from earlier amendments, subject to licensed-text confirmation; no A4-specific V2X/PME change is asserted on this page.

How this is made and proven compliant

What governs it
  • BS 7671 Chapter 54 (§542 earthing arrangements, §544 protective bonding conductors) and Chapter 41 (§411 automatic disconnection of supply)
  • BS 7671 §551.4.3.2.1 (independent means of earthing for an island/switched-alternative source) and §722.411.4.1 (PME / open-PEN protective measures)
  • BS 7430 (electrode selection and resistance) read with BS 7671 §542.2.2 / §542.2.4 and Table 41.5, for the TT-island route
Who may do it

Design, installation, inspection and testing by a competent person. Altering the earthing arrangement, adding a changeover or altering the consumer unit is normally notifiable under Part P (England; Wales, Scotland and Northern Ireland differ).

How compliance is demonstrated
  • Initial verification to BS 7671 Part 6 with an Electrical Installation Certificate
  • RCD operation proven by test in both grid and V2L modes
  • For a TT island: electrode resistance (Ra) measured low and stable enough for reliable disconnection
  • Continuity of every protective conductor confirmed; one — and only one — neutral-earth bond confirmed live only when on V2L
  • No metallic bridge (pipe, structure or cable armour) between two earth systems
Confidence & currency

Confidence: Inference rolled up across the clauses cited above (the strictest state wins).

Frequently asked questions

Why does a V2L output need its own earth reference at all?

Because it is a separately derived source. The grid's neutral-earth reference is made at the substation; a floating V2L output has none, so until one bond is supplied there is nothing for an earth fault to return to and no RCD protection — even though a plug-in socket tester will show 'all good'.

Why is bonding the V2L neutral to earth correct when it feels wrong?

It is the source reference — the exact equivalent of the substation transformer's earthed star point, made for your own source. Make one bond, on the source side, in circuit only on V2L, so you never have two earth references in parallel.

Can I ever switch the earth in the changeover?

No. The changeover switches line and neutral between grid and V2L; the protective conductor (earth/CPC) stays continuous and is never switched. The only earth-side element that changes between modes is *where the single neutral-earth bond is made* — never whether an earth exists.

Why can't I just drive an earth spike for an indoor board?

Because a single indoor TT sub-board creates a simultaneous-reach hazard with the rest of the PME-earthed installation. Indoors you keep one earth and use an isolation transformer; the TT route is for a genuinely separate outbuilding, designed and proven by test.

How is the earthing actually proven safe?

By test, not by reasoning. RCD operation is confirmed in both grid and V2L modes; for a TT island, the electrode resistance (Ra) is measured low and stable enough for reliable disconnection; and the competent person confirms exactly one neutral-earth bond, continuous CPCs and no metallic bridge between earth systems.

Last reviewed
14 June 2026
Written against
BS 7671:2018 + A4:2026
Reviewed by
Martin (qualified UK electrician)
Next review due
14 December 2026

General information, not project-specific design advice. Standards are cited by reference only and never reproduced. How we source this.

References & sources (4)
  1. BS 7671:2018+A4:2026 — Requirements for Electrical Installations (IET/BSI)cited by clause only; standard text not reproduced
  2. IET — Amendment 4 updates to the 18th Edition
  3. BS 7430:2026 — Protective earthing of electrical installations (Code of Practice, BSI)cited by topic; 2026 clause numbers not confirmed; standard text not reproduced
  4. V2L Workshop technical reference (internal) — verified design facts and confidence flags